Skip to content
THE KIT. THE ANALYSIS. THE ANSWER.(562) 404-9955
Amalina TechnologiesSAMPLING & ANALYSIS

Refrigerant purity, judged against the limits for your fluid

Purity and contamination testing to AHRI Standard 700. 7 characteristics, measured against the row of the table that belongs to the refrigerant you actually sent — not against one generic column applied to everything.

01What is measured

The 7 characteristics

The basis matters as much as the number, so it is reported with it, and the determination named on each line is the one the standard defines for that characteristic. What each line tends to mean about the system it came out of is our reading, not the standard's.

01

vapor phase

Air and other non-condensables

Basis % by volume @ 25.0 °C

Determination Gas chromatography — separate vapor-phase sample

Air. It comes in through a low-side leak, a recovery machine left open between jobs, or a cylinder nobody evacuated. It is also the one characteristic that cannot be read off the liquid sample, which is why it needs its own draw.

02

liquid phase

Water

Basis ppm by weight

Determination Karl Fischer titration

Moisture, and therefore acid before long — water hydrolyses with the refrigerant and with the oil. A water result over the limit usually predicts the acidity result on the line below it. A drier that has already changed color has told you half of this for free.

03

liquid phase

All other volatile impurities

Basis % by weight

Determination Gas chromatography

Something present that is not the labeled refrigerant, most often another refrigerant. Recovery cylinders that were never dedicated to one fluid are the usual source, and the resulting mixture is worth far less than either fluid alone.

04

liquid phase

High boiling residue

Basis % by volume or % by weight

Determination Gravimetric — the basis used must be recorded

Oil that traveled with the charge — typically off a recovery machine, or from pulling liquid out of a flooded system. It is measured gravimetrically, and the basis used is recorded because the standard permits two.

05

liquid phase

Particulates and solids

Basis pass/fail

Determination Visual

Metal fines, desiccant dust, rust off the inside of the cylinder. A visual determination against the standard's own wording, reported as that wording rather than as a number we invented.

06

liquid phase

Acidity

Basis ppm by weight as HCl

Determination Titration — detection limit 0.1 ppm on a 50–60 g sample

Acid, reported as HCl. After a hermetic motor burnout this is the line that decides whether a recovered charge is worth reclaiming or is scrap, and it is the line a buyer will ask about first.

07

liquid phase

Chloride

Basis pass/fail

Determination Turbidity — turbidity appears at roughly 3 ppm by weight

Chloride, as turbidity. It tends to appear alongside acidity when a chlorinated fluid has broken down, and it is a pass/fail determination — the standard does not define a reportable number for it.

2 of the 7 are pass/fail by definition and the rest are numbers. Note what is noton the list: there is no “purity, minimum” characteristic in AHRI 700. The figure everyone quotes is the arithmetic complement of the 0.5% by weight cap on other volatile impurities, and for a blend it is the wrong test entirely.

02Liquid draw, vapor draw

One cylinder cannot answer all 7

This is the part most sampling instructions skip, and it is the part that decides whether your non-condensables number means anything at all.

Draw 6 of 7 from the liquid valve

Liquid phase

Water, All other volatile impurities, High boiling residue, Particulates and solids, Acidity, Chloride. All of them are liquid-phase determinations, which is why the procedure specifies the Liquid valve and a fill of 7580%.

There is a second reason, and it matters more than the first: a zeotropic blend does not carry the same composition in the vapor as it does in the liquid. Draw vapor off a blend and you will measure a composition the cylinder does not contain, then fail it against a window it never left.

One characteristic needs its own sample

Air and other non-condensables

Basis: % by volume @ 25.0 °C. Determination: Gas chromatography — separate vapor-phase sample. Because the basis is defined on the vapor at a stated temperature, the source temperature at the moment of draw is part of the record — send it with the sample, and we will report it with the result. A non-condensables figure with no source temperature behind it is a number, not a measurement.

It is also the one line a laboratory can quietly not run. If a report shows a non-condensables result but the sampling instructions only ever asked for a liquid draw, the two statements do not fit together.

Low-pressure fluids, dry nitrogen, and why that is not a contradiction

Our own procedure allows it: For low-pressure refrigerant, the source tank may be pressurized through the Vapor valve with dry nitrogen. Pushing a sample with nitrogen sounds like the last thing you would do before an air test — and it would be, except that the fluids needing that treatment are the same fluids AHRI 700 exempts from the non-condensables characteristic, because their normal boiling point is at or above room temperature: R-11, R-113, R-123, R-141b, R-245fa, R-1233zd(E). For those, non-condensables are reported as Not Applicable — never as a pass, never as a blank.

The corollary is the part to take away: never use nitrogen to move a high-pressure sample whose air result you intend to rely on. And check the edition — AHRI 700-2024 exempts 3 fluids the federally incorporated appendix does not (R-1336mzz(Z), R-1336mzz(E), R-514A), so the same sample can be Not Applicable under one edition and testable under another.

03Why the fluid changes the answer

A generic limit column passes and fails the wrong material

Of the 22 single-component refrigerants in the published table, 7 carry at least one limit that differs from the set most reports print as universal.

Single-component fluids whose limits are not the common set of 10 ppm water, 1 ppm acidity, 0.5% other volatiles and 1.5% non-condensables. Departures from that set are set in bold.
RefrigerantWaterppm by weightAcidityppm by weight as HClAll other volatile impurities% by weightAir and other non-condensables% by volume @ 25.0 °C
R-1120 — differs from the common set10.5Not applicable
R-11320 — differs from the common set10.5Not applicable
R-12320 — differs from the common set10.5Not applicable
R-141b100 — differs from the common set10.9 — differs from the common setNot applicable
R-142b15 — differs from the common set3 — differs from the common set0.52.0
R-245fa20 — differs from the common set10.5Not applicable
R-1233zd(E)20 — differs from the common set10.5Not applicable

Read the R-11 and R-123 rows in particular: a larger water allowance than the common set, and no non-condensables test at all. Hold a low-pressure charge to the common water limit and you fail material the standard passes; report a pass on non-condensables for those fluids and you have reported a test the standard never asked for. One generic limit column produces both mistakes.

Blends are judged on composition, not purity

Every blend shares the same contaminant limits. What decides the result is a two-sided window on each named component, plus the 0.5% by weight cap on anything that is not one of them. A blend can be 99.5% pure and fail — and a purity figure on its own cannot show you why.

The two below are both nominally 50/50 and both windows are skewed, in opposite directions. Anything implemented as nominal ± tolerance is wrong for both of them, which is why we store and publish explicit minima and maxima for all 25 blends.

Every window, published in full

R-410A

R-410A component composition windows, % by weight
ComponentNominalAllowable
R-3250.048.550.5
R-12550.049.551.5

% by weight

R-507A

R-507A component composition windows, % by weight
ComponentNominalAllowable
R-12550.049.551.5
R-143a50.048.550.5

% by weight

04The certification

What it means, and how to check it without asking us

Amalina Technologies is an AHRI Certified® Refrigerant Testing Laboratory, and the only one in California. This service is what that certification covers.

It is a listing, not a letterhead

AHRI publishes the participating laboratories in a directory that anyone can search. We do not print certificate numbers on this site; a number on a web page proves nothing about whether it is still current, and the register does.

Search the directory (opens in new tab)

It covers refrigerant testing

This service, and this service only. The program has no oil scope, so nothing on our oil analysis pages claims it. If you need a certified result, it is this service that carries one.

Tell us which edition binds you

40 CFR 82 subpart F, Appendix A is the text incorporated federally; AHRI 700-2019 and AHRI 700-2024 are not identical to it or to each other. Say which one your obligation runs against in the notes when you register the sample, and the result will be read against that one.

Disclosure: we share common ownership with a refrigerant reclaimer in the adjacent unit of this building, and the purity we report on a batch is an input to what that company pays for it. That is exactly the kind of arrangement a customer should be told about rather than left to discover. How the laboratory is kept separate.

05Who sends us samples

Three decisions this test is bought to settle

Reclaimers, verifying a batch before it is sold

Whether this batch can go out the door. The limits are the ones incorporated federally for Section 608 work — 40 CFR 82 subpart F, Appendix A — so the laboratory behind the number ends up in the batch record rather than in a file nobody reopens.

Lines that decide it
Every line, plus composition on every blend.

Contractors, deciding whether recovered gas is worth reclaiming

Whether a drum of recovered material has value or is a disposal cost. A test settles it before the drum moves; skipping it means finding out once the material has already been shipped, and moving the same drum twice.

Lines that decide it
All other volatile impurities first — mixed cylinders are the usual finding — then water and acidity.

Building owners and facility engineers, after a compressor burnout

Whether the charge sitting in recovery drums can go back into a machine, and whether the clean-up is finished. The refrigerant answers the first half; the oil sample answers the second, and no refrigerant result substitutes for it.

Lines that decide it
Acidity, chloride, water, high boiling residue.

06What comes back

The report, and what is on every line of it

Written to be read by the person who took the sample and by whoever asks them about it afterwards.

  • The refrigerant as declared, and the limit set applied to it — the row of the published table belonging to that fluid, not a house set.
  • A line for each of the 7 characteristics: the measured value, the limit it was judged against, and the basis of both.
  • A verdict on each line. Where a characteristic does not apply to your fluid, the line reads Not Applicable — never a pass, never a blank.
  • For blends, each named component against its own two-sided window, plus the cap on anything not named. Composition is the verdict.
  • The source temperature recorded at sampling, carried onto the report because the non-condensables basis is defined at a stated temperature.
  • The R-40 sub-limit where the applicable edition carries it, reported as what it is rather than labeled a federal requirement it is not.

A result exactly at the limit passes. We publish that rule, and the rest of them, in advance — the time to agree how a close result will be read is before the sample is drawn, not after the number arrives.

Before you send anything

  • The full limit table →

    All 22 single-component fluids and 25 blends, with the decision rules that govern a close result. This is the bar your sample will be held to, published before you pay for anything.

  • An example report →

    Our report format, reproduced on an illustrative sample and annotated line by line, so nothing on the document that comes back needs explaining over the phone.

  • Refrigerant or oil? →

    The two services compared side by side, keyed to what you are actually looking at on the machine.

07Your part

Taking the sample

The sample is the half of this we cannot do for you, and a bad one produces a confident number about something that was never in the machine. The full procedure is published — this is the shape of it.

  1. Register it first

    Log the fluid, the system it came from and where the report goes, before the cylinder travels. It arrives already identified, and you hold your own record of what you sent.

  2. Use the laboratory cylinder

    The laboratory-supplied cylinder is the standard route, and it comes back to us with the sample inside. A cylinder of your own is accepted only if it is rated to at least 400 psi, evacuated to 50 microns or better, and dedicated to sampling — a cylinder of unknown history carries whatever was in it last, and that is declared under Notes when you register.

  3. Evacuate to 50 microns

    Or better. Anything left in the cylinder is something we will find and report against your material — most obviously as air, which is the line evacuation exists to protect.

  4. Draw from the liquid valve

    Liquid, not vapor. 6 of the 7 characteristics are liquid-phase determinations, and a blend sampled as vapor will report a composition the cylinder does not contain.

  5. Fill to 75–80%

    About 350 g. Enough material to run every characteristic, and enough headspace that the cylinder is not liquid-full when it warms up in a van.

  6. Record the source temperature

    At the moment of the draw, and send it with the sample. If the non-condensables result matters to you, that figure and a separate vapor draw are what make it a measurement.

Refrigerant analysis

Send the cylinder, get the row that belongs to your fluid

Registered before it travels, judged against the published limits for the refrigerant you actually sent, and reported line by line with the basis of every number on it.